Storage Dynamics

Charge Balance

The stored energy evolves over time according to charging, discharging, and self-discharge losses:

\[ E_{s,t+1} = E_{s,t} \left(1 - \delta_s\right)^{\Delta t_t} + P^{\text{c}}_{s,t} \, \eta^{\text{c}}_s \, \Delta t_t - \frac{P^{\text{d}}_{s,t}}{\eta^{\text{d}}_s} \, \Delta t_t \]

where:

  • \(E_{s,t}\) — stored energy at the start of timestep \(t\)
  • \(P^{\text{c}}_{s,t}\) — charging flow rate (energy entering the storage)
  • \(P^{\text{d}}_{s,t}\) — discharging flow rate (energy leaving the storage)
  • \(\eta^{\text{c}}_s\) — charging efficiency (losses during charging)
  • \(\eta^{\text{d}}_s\) — discharging efficiency (losses during discharging)
  • \(\delta_s \in [0, 1]\) — self-discharge rate per hour
  • \(\Delta t_t\) — timestep duration in hours

The charge state has \(|\mathcal{T}| + 1\) values (one before each timestep plus one after the last timestep).

Charge State Bounds

The charge state is bounded by relative SOC limits scaled by the storage capacity:

\[ \bar{\mathrm{E}}_s \cdot \underline{\mathrm{e}}_s \leq E_{s,t} \leq \bar{\mathrm{E}}_s \cdot \bar{\mathrm{e}}_s \quad \forall \, s, t \]

Initial & Cyclic Conditions

Fixed initial state:

\[ E_{s,t_0} = E_0 \]

where \(E_0\) is Storage.prior_level (absolute MWh). If prior_level is None, the initial level is unconstrained (the optimizer chooses).

Cyclic condition (when Storage.cyclic = True):

\[ E_{s,t_{\text{end}}} = E_{s,t_0} \]

This ensures the storage ends at the same level it started.

Final level bounds (final_level_min / final_level_max) — absolute bounds [MWh] on the level at the last timestep, per period:

\[ \underline{\mathrm{E}}^{\text{end}}_s \leq E_{s,t_{\text{end}}} \leq \bar{\mathrm{E}}^{\text{end}}_s \]

They compose with cyclic (the prior level is then bounded too, since \(E_{s,t_0} = E_{s,t_{\text{end}}}\)).

Simultaneous Charge & Discharge

With \(\eta^{\text{c}} \cdot \eta^{\text{d}} < 1\), charging and discharging at once destroys energy — occasionally optimal (e.g. under must-run surplus) but physically impossible for most devices. prevent_simultaneous = True excludes it with a binary \(b_{s,t}\) per timestep:

\[ P^{\text{c}}_{s,t} \leq \mathrm{M}^{\text{c}}_s \cdot b_{s,t} \qquad P^{\text{d}}_{s,t} \leq \mathrm{M}^{\text{d}}_s \cdot (1 - b_{s,t}) \]

where \(\mathrm{M}\) is the static size bound of the respective flow (fixed size, or the sizing/investment maximum). Both flows must therefore be sized.

Consider a soft penalty first

The binary turns the model into a MILP. In most models simultaneous cycling only pays off under negative prices or must-run surplus — a small penalty on the charge/discharge flows (effects_per_flow_hour={'penalty': 1e-3}) usually discourages it while keeping the problem linear and the real cost accounting clean (this is PyPSA's recommended approach; cf. Parzen et al. 2023 on unintended storage cycling). Reach for prevent_simultaneous when the exclusion must be exact.

Parameters

Symbol Description Reference
\(E_{s,t}\) Stored energy variable storage--level[storage, time]
\(P^{\text{c}}_{s,t}\) Charging flow rate flow--rate[charge_flow, time]
\(P^{\text{d}}_{s,t}\) Discharging flow rate flow--rate[discharge_flow, time]
\(\bar{\mathrm{E}}_s\) Storage capacity Storage.capacity
\(\eta^{\text{c}}_s\) Charging efficiency Storage.eta_charge
\(\eta^{\text{d}}_s\) Discharging efficiency Storage.eta_discharge
\(\delta_s\) Self-discharge rate Storage.relative_loss_per_hour
\(\underline{\mathrm{e}}_s\) Relative min SOC Storage.relative_level_min
\(\bar{\mathrm{e}}_s\) Relative max SOC Storage.relative_level_max
\(\underline{\mathrm{E}}^{\text{end}}_s\) Min final level [MWh] Storage.final_level_min
\(\bar{\mathrm{E}}^{\text{end}}_s\) Max final level [MWh] Storage.final_level_max
\(b_{s,t}\) Charging indicator binary Storage.prevent_simultaneous
\(\Delta t_t\) Timestep duration dt

See Notation for the full symbol table.

Example

A battery with \(\bar{\mathrm{E}} = 10\) MWh, \(\eta^{\text{c}} = 0.95\), \(\eta^{\text{d}} = 0.95\), \(\delta = 0.001\)/h, \(\Delta t = 1\) h:

Starting at \(E_0 = 5\) MWh, charging at \(P^{\text{c}} = 2\) MW:

\[ E_1 = 5 \times (1 - 0.001)^{1} + 2 \times 0.95 \times 1 = 4.995 + 1.9 = 6.895 \; \text{MWh} \]